- 1.Uhlaka
I-VSM-12 series unomphela uzibuthe-uhlobo lwasendlini high voltage vacuum circuit breaker iyisigaba ezintathu AC 50Hz, voltage ukalwe 12kV endlini switch imishini. Kufakwe ngendlela enozibuthe ehlala njalo yenkampani yethu ucwaningo nokuthuthukiswa kwamabhizinisi ezimboni nezimayini, ukuphehla ugesi kanye nezindawo zesiteshi esincane njengezinhloso zokulawula nokuvikela ugesi. Umkhiqizo onokwethenjelwa okuphezulu kanye nezici zempilo ende, ikakhulukazi ezindaweni ezinezimo ezibucayi, njengokusebenza njalo, ukuphindaphinda kwe-short-circuit breaking current.
- 2.Izimo Zemvelo
◆Izinga lokushisa le-ambient: -25℃~+40℃;
◆Ukuphakama: ≤1000m, uhlobo lwethafa ≤3000m;
◆Umswakama ohlobene: isilinganiso sansuku zonke ≤95%, isilinganiso sanyanga zonke ≤90%, ukucindezela komhwamuko ogcwele nsuku zonke
isilinganiso ≤2.2×10 MPa, isilinganiso sanyanga zonke ≤1.8×10MPa. Lapho izinga lokushisa lehla ngokushesha phakathi
izinga lokushisa eliphezulu, kungase kwenzeke condensation.
◆Amandla okuzamazama komhlaba: ≤8 izinga;
◆Izindawo ezingenamlilo, ubungozi bokuqhuma, ukungcola okukhulu, ukugqwala kwamakhemikhali, kanye nokunamandla
ukudlidliza.
3. Uhlobo Incazelo
4. Imingcele Eyinhloko Yezobuchwepheshe
◆ Imingcele yezobuchwepheshe ye-vacuum circuit breaker
Cha | Into | Amayunithi | Amapharamitha | ||||
1 | I-voltage elinganiselwe | kV | 12 | ||||
2 | Izinga lokwahlukanisa elilinganiselwe | 1min imvamisa yamandla imelana ne-voltage | 75 | ||||
Isilinganiso sombani simelana ne-voltage | 42 | ||||||
3 | Ikalwe okwamanje | A | 630 ~ 1250 | 1250~3150 | 1250~4000* | ||
4 | Ilinganiswe ngokuphuka kwesiyingi esifushane | kA | 20 | 31.5 | 40 | 50 | |
5 | Isilinganiso sokuvala isiyingi esifushane(ukuphakama) | 50 | 80 | 100 | 125 | ||
6 | Ikalwe ngokuzinza okuguquguqukayo okwamanje(isilinganiso esiphezulu) | 50 | 80 | 100 | 125 | ||
7 | I-thermal stability current (RMS) elinganiselwe | 20 | 31.5 | 40 | 50 | ||
8 | Ilinganiselwe ngokunqamuka kwenombolo ye-short-circuit breaking | Izikhathi | 30 | 30 | 20 | 20 | |
9 | Ilinganiselwe isikhathi sokuzinza kwe-thermal | S | 4 | ||||
10 | Kukalwe ukulandelana kokusebenza |
| O-0.3s-CO-180s-CO | ||||
11 | Impilo yemishini | Izikhathi | ≥30000 | ||||
12 | Impilo yemishini yomshini kazibuthe unomphela kanye nengxenye yokudlulisela | Izikhathi | ≥100000 | ||||
13 | Ilinganiselwe i-single capacitor bank breaking current | A | 630 ~ 1250 | ||||
14 | Ilinganiselwe i-back-to-back capacitor breaking current | 400 | |||||
15 | Ikalwe ngaphandle kwesinyathelo sokunqamuka kwamanje | kA | 12.6 16 |
*Uma kulinganiswa okwamanje >3150A, kufanele kube nezinyathelo zokungenisa umoya.
**Kunomehluko ngenxa yeziphazamisi ze-vacuum ezihlukene.
◆ Amapharamitha wezakhiwo zemishini ngemva kokulungiswa
Cha | Into | Amayunithi | Amapharamitha |
1 | Ibanga lokusula phakathi koxhumana nabo abavuliwe | mm | 11±1* |
2 | Xhumana nohambo | 3.5±0.5 | |
3 | I-synchronism yokuvula izigaba ezintathu | ms | ≤2 |
4 | Ukuvala isikhathi sokugxuma othintana naye | ≤2 ≤3(40kA) | |
5 | Ibanga eliphakathi kwezigaba | mm | 210, 275 |
6 | Ukuvala ukucindezela kothintana naye | N | 20kA 31.5kA 40kA 2000±200 3100±200 4500±300 |
7 | Ukumelana okuyinhloko kwesekethe ye-conductive | mΩ | 60 45 30 |
8 | Isivinini sokuvula esimaphakathi | m/s | 1.1±0.2 |
9 | Isivinini sokuvala esimaphakathi | 0.7±0.2 0.8±0.2 | |
10 | Isikhathi sokuvula | ms | 30-60 |
11 | Isikhathi sokuvala | 50~100 | |
12 | Ukuqina nokuqina kokuxhumana okuqinile okuvunyelwe ukuguga | mm | 3 |
Kunomehluko ngenxa yeziphazamisi ze-vacuum ezihlukene.
◆ Amapharamitha wobuchwepheshe wemishini kazibuthe yaphakade
Igama | Amandla kagesi | Into | Iyunithi | I | II | III | ||
20kA | 25kA | 31.5kA | 40kA | 50kA | ||||
Ikhoyili yokuvala | I-DC220V | ukusebenza kwamanje (isiqongo) | A | 52 | 88 | |||
Ukumelana | Oh | 4.2±0.18 | 2.5±0.18 | |||||
Ikhoyili yokuvula | I-DC220V | ukusebenza kwamanje (isiqongo) | A | 2 | 3.5 | |||
Ukumelana | Oh | 120±15 | 600±0.5 | |||||
Ikhoyili yokuvala | I-AC220V | Okokufaka kwamanje | A | ≤2 |
| |||
Ikhoyili yokuvula | I-AC220V | ukusebenza kwamanje (isiqongo) | A | 2 | 3.5 | |||
Ukumelana | Oh | 120±15 | 60±5 | |||||
Qaphela: uma unezidingo ezikhethekile zokuphakelwa kukagesi, sicela ucacise lapho u-oda.
5. Umdwebo Wesakhiwo Esijwayelekile (iyunithi: mm)
◆ Uhlobo olungahoxiswa (isigxobo esivamile) (ububanzi bekhabhinethi 800 noma 1000mm)
Ibanga eliphakathi kwesigaba 210mm (275mm)
Ikalwe okwamanje (A) | 630 | 1250 | 1600 |
Isilinganiso se-short-circuit breaking current (kA) | 20, 25, 31.5 | 20, 25, 31.5, 40 | 31.5, 40 |
Kufaniswe usayizi wokuxhumana ongashintshi (mm) | F35 | F49 | F55 |
◆Uhlobo olungahoxiswa (isigxobo esivamile) (ububanzi bekhabhinethi 1000mm)
Ibanga phakathi kwesigaba 275mm
Ikalwe okwamanje (A) | 1600 | 2000 | 2500 | 3150 | 4000* |
Isilinganiso se-short-circuit breaking current (kA) | 31.5 | 40 | 40, 50 | ||
Kufaniswe usayizi wokuxhumana ongashintshi (mm) | F79 | F109 |
*Uma ikalwe okwamanje>3150A, idinga ukupholiswa komoya okuphoqelekile.
◆Uhlobo olungaguquki (isigxobo esivamile)
Ibanga eliphakathi kwesigaba 210mm (275mm)
Ikalwe okwamanje (A) | 630 | 1250 | 1600 |
Isilinganiso se-short-circuit breaking current (kA) | 20, 25, 31.5 | 20, 25, 31.5, 40 | 31.5, 40 |
◆Uhlobo Olugxilile (isigxobo esivamile)
Ibanga phakathi kwesigaba 275mm
Ikalwe okwamanje (A) | 1600 | 2000 | 2500 | 3150 | 4000* |
Isilinganiso se-short-circuit breaking current (kA) | 31.5 | 40 | 40, 50 |
*Uma ikalwe okwamanje>3150A, idinga ukupholiswa komoya okuphoqelekile.
◆Uhlobo olungahoxiswa (isigxobo esishumekiwe) (ububanzi bekhabhinethi 800 noma 1000mm)
Ibanga eliphakathi kwesigaba 210mm (275mm)
Ikalwe okwamanje (A) | 630 | 1250 | 1600 |
Isilinganiso se-short-circuit breaking current (kA) | 20, 25, 31.5 | 20, 25, 31.5, 40 | 31.5, 40 |
Kufaniswe usayizi wokuxhumana ongashintshi (mm) | F35 | F49 | F55 |
◆Uhlobo olungahoxiswa (isigxobo esishumekiwe) (ububanzi bekhabhinethi 1000mm)
Ibanga phakathi kwesigaba 275mm
Ikalwe okwamanje (A) | 1600 | 2000 | 2500 | 3150 | 4000* |
Isilinganiso se-short-circuit breaking current (kA) | 31.5 | 40 | 40, 50 | ||
ukufanisa usayizi wokuxhumana ongashintshi (mm) | F79 | F109 |
*Uma ikalwe okwamanje>3150A, idinga ukupholiswa komoya okuphoqelekile.
◆Uhlobo olungaguquki (isigxobo esishunyekiwe)
Ibanga eliphakathi kwesigaba 210mm (275mm)
Ikalwe okwamanje (A) | 630 | 1250 | 1600 |
Isilinganiso se-short-circuit breaking current (kA) | 20, 25, 31.5 | 20, 25, 31.5, 40 | 31.5, 40 |
◆Uhlobo olungaguquki (isigxobo esishunyekiwe)
Ibanga phakathi kwesigaba 275mm
Ikalwe okwamanje (A) | 1600 | 2000 | 2500 | 3150 | 4000* |
Isilinganiso se-short-circuit breaking current (kA) | 31.5 | 40 | 40, 50 |
*Uma ikalwe okwamanje>3150A, idinga ukupholiswa komoya okuphoqelekile.