Isifinyezo
Imikhiqizo yethu emisha, i-NVS1-12 series vacuum vacuum breaker yasendlini isetshenziselwa ama-switchgears ohlelweni lwamandla angu-12kV, njengeyunithi yokulawula nokuvikela impahla kagesi emabhizinisini ezimboni nezimayini, izitshalo zikagesi neziteshi ezincane. Ngenxa yezinzuzo ezikhethekile ze-vacuum circuit breaker, ifaneleka ngokukhethekile ukusebenza okuvamisile okudinga isilinganiso samanje sokusebenza, noma izindawo lapho i-short-circuit current iphulwa izikhathi eziningi. I-circuit breaker yamukela umklamo ohlanganisiwe wendlela yokusebenza kanye nomzimba we-circuit breaker. Zombili ziyisakhiwo sangaphambili nangemuva, esinomsebenzi othembekile wokuxhumanisa. I-circuit breaker ingasetshenziswa njengeyunithi yokufaka engaguquki. Ingase futhi ifakwe iloli lika-chassis ibe iyunithi yenqola yesandla.
Izindinganiso zomkhiqizo
I-GB/T1984-2014 I-voltage ephezulu ye-AC Circuit Breaker
I-JB/T3855-2008 3.6-40.5kV yasendlini i-AC High voltage vacuum circuit breaker
DL/T403-2000 12kV-40.5kV high voltage vacuum circuit breaker iyala izimo zobuchwepheshe
I-IEC62271-100:2008 I-High Voltage Switchgear kanye ne-Controlgear Ingxenye 100: I-AC Circuit-breakers
Izimo Zemvelo
Izinga lokushisa le-ambient: -15 C ~+40C
O Umswakama we-ambient: Umswakama omaphakathi wansuku zonke ohlobene
Isilinganiso sansuku zonke sokucindezela komhwamuko
O Altitude ≤ 1000m;
O Amandla okuzamazama komhlaba
O Indawo yokufaka: Indawo akufanele ibe nengozi yokuchitheka kwamanzi, ukungcola okukhulu, ukugqwala kwamakhemikhali kanye nokuzamazama okumangalisayo.
Imingcele Eyinhloko Yezobuchwepheshe
Into | Iyunithi | Idatha |
I-voltage elinganiselwe | kV | 12 |
Isilinganiso sokuvama | Hz | 50 |
Ilinganiselwe iminithi elingu-1 imvamisa yamandla imelana ne-voltage (isigaba ukuya esigabeni, emhlabeni, ukuphuka) | kV | 42 |
Isilinganiso sombani imelana ne-voltage (isigaba ukuya esigabeni, emhlabeni, ukuphuka) | kV | 75 |
Ilinganiswe ngokulandelana komsebenzi | Ot-YINI-t'-YINI |
Into | Iyunithi | I-NVS1-12 | ||||||||||||
Ikalwe okwamanje | A | 630 | 1250 | 1250 | 1600 | 2000 | 2500 | 1250 | 1600 | 2000 | 2500 | 3150 | 3150 | 4000 |
Ilinganiselwe ngokuphulwa kwesekethe emfushane | kA | 20/25 | 31.5 | 40 | 50 | |||||||||
Ilinganiselwe isekethe emfishane eyenza yamanje (isiqongo) | kA | 50/63 | 80 | 100 | 125 | |||||||||
Isikhathi esilinganiselwe sokujikeleza okufushane | s | 4 | 4 | 4 | 4 | |||||||||
Ilinganiswe izikhathi ezimfushane zokuphulwa kwesekethe | isikhathi | 50 | 50 | 30 | 20 | |||||||||
Impilo yemishini | isikhathi | 20000 | 20000 | 20000 | 10000 |
Qaphela:
20/25/31.5kA, t=0.3s t'=180s
40/50kA, t=180s, t'=180s
I-4000A VCB idinga ukupholisa umoya ngempoqo
Into | Iyunithi | Idatha | ||||
Ukusula phakathi koxhumana nabo abavuliwe | mm | 9±1 | ||||
Ukuhamba ngaphezulu | 3.5±0.5 | |||||
I-asynchronism yezigaba ezintathu zokuvula nokuvala | ms | ≤2 | ||||
Isikhathi sokuvala othintana naye | ms | ≤2 (50kA) | ||||
Ingcindezi yokuxhumana yokuvala abathintwayo | N | 20kA | 25 kA | 31.5 kA | 40 kA | 50 kA |
2000±200 | 2400±200 | 3100±200 | 4250±250 | 5500±300 | ||
Isivinini sokuvula esimaphakathi | m/s | 0.9~1.3 | ||||
Isivinini sokuvala esimaphakathi | 0.4~0.8 |