Okujwayelekile
I-KYN61-40.5 uhlobo lwensimbi oluvale insimbi olukhiphekayo lwe-AC oluvalwe ngensimbi (ngemuva kwalokhu olubizwa ngokuthi "switchgear") lubonakala ikakhulukazi ngokusetshenziswa kwe-ZN85-40.5 ama-vacuum breaker avaleleke ngokuphelele kanye nezindlela zokusebenza zasentwasahlobo ekhabhinethi, kanye nomzimba wekhabhinethi. ihlanganiswe ngensimbi eboshwe ngepulasitiki, ethuthukisa ukunemba okufanayo kwe-VCB nekhabhinethi. I-VCB kulula ukuyiphusha nokuyikhipha futhi inokuhwebelana okuqinile nokubukeka okuhle, izixazululo eziphelele, ukusetshenziswa okuphephile nokuthembekile.
Lo mkhiqizo usetshenziswa kusistimu yamandla engu-35kV yezigaba ezintathu ze-AC 50Hz. Isetshenziselwa ukwamukela nokusabalalisa amandla kagesi ezitshalweni zikagesi, iziteshi ezincane kanye namagumbi okusabalalisa amandla ezinkampani zezimboni nezimayini. Inokulawula, ukuvikela kanye nemisebenzi yokuqapha. Lo mkhiqizo uhambisana nezindinganiso: GB3906 "I-alternating-current metal-enclosed switchgear kanye negiya lokulawula lamandla kagesi akalwe ngaphezu kuka-3.6kV nokufika futhi ahlanganise 40.5kV", GB/T11022 "Izincazelo ezivamile ze-high-voltage switchgear kanye namazinga okulawula", DL/ I-T404 "I-switchgear yensimbi eshintshayo yamanje kanye negiya lokulawula elilinganiselwe ngaphezu kuka-3.6kV nokufika futhi kuhlanganise no-40.5kV", IEC60298 "I-AC metal-enclosed switchgear kanye negiya lokulawula lama-voltage akalwe ngaphezu kuka-1 kV nokufika futhi kuhlanganise no-52kV".
Imibandela Yokusebenzisa Okuvamile
● Izinga lokushisa lomoya elizungezile: -15℃~+40℃.
● Izimo zokuswakama:
Umswakama ojwayelekile wansuku zonke ohlobene: ≤95%, isilinganiso sansuku zonke sokucindezela komhwamuko wamanzi ≤2.2kPa.
Isilinganiso sanyanga zonke somswakama ohlobene singama-90%, futhi isilinganiso sanyanga zonke sokucindezela komhwamuko wamanzi ngu-1.8kPa.
● Ukuphakama: ≤4000m.
● Amandla okuzamazama komhlaba: ≤8 degrees.
● Umoya ozungezile akufanele ungcoliswe igesi ebolayo noma evuthayo, umhwamuko wamanzi, njll.
● Izindawo ezingenakho ukudlidliza okuvamile.
Uhlobo Incazelo
Imingcele Eyinhloko Yezobuchwepheshe
Into | Iyunithi | Inani | |
I-voltage elinganiselwe | kV | 40.5 | |
Ikalwe okwamanje | Ikalwe okwamanje yebhasi elikhulu | A | 630, 1250, 1600 |
Isilinganiso samanje se-circuit breaker ehlomile | A | 630, 1250, 1600 | |
Izinga le-insulation | I-1min yamandla efrikhwensi imelana ne-voltage: isigaba-kuya-isigaba, isigaba-kuya-emhlabeni/kuzo zonke othintana nabo abavulekile | kV | 95/110 |
Umfutho wombani umelana ne-voltage (ukuphakama):isigaba-kuya-isigaba, isigaba ukuya emhlabeni,/kuzo zonke izindawo ezivulekile othintana nazo | kV | 185/215 | |
Imvamisa yamandla imelana ne-voltage yesifunda esisizayo kanye nesifunda sokulawula | V/1 iminithi | 2000 | |
Isilinganiso sokuvama | Hz | 50 | |
Ilinganiselwe ngokuphulwa kwesekethe emfushane | kA | 20, 25, 31.5 | |
Ilinganiselwe isikhathi esifushane ukumelana nobude besikhathi samanje/esilinganiselwe sesiyingi esifushane | kA/4s | 20, 25, 31.5 | |
Isilinganiso esiphakeme sokumelana nokumelana namanje | kA | 50, 63, 80 | |
Ilinganiselwe isekethe emfushane yokwenza yamanje | kA | 50, 63, 80 | |
I-voltage elinganiselwe yesekethe yokulawula | IN | DC110/220, AC110/220 | |
Idigri yokuvikela | I-switchgear ebiyelwe | IP4X | |
Igumbi (lapho iminyango ivulwa) | IP2X |
Imingcele Eyinhloko Yezobuchwepheshe
Amapharamitha Wobuchwepheshe we-ZN85-40.5 Uhlobo Lwesiqhekezi Sesekhethi ene-Spring Operating Mechanism(Ihlanganisiwe)
Into | Iyunithi | Inani | |
I-voltage elinganiselwe | kV | 40.5 | |
Ikalwe okwamanje | A | 630, 1250, 1600 | |
Izinga le-insulation | I-1min yamandla efrikhwensi imelana ne-voltage: isigaba-kuya-isigaba, isigaba-kuya-emhlabeni/kuzo zonke othintana nabo abavulekile | kV | 95/110 |
Umfutho wombani umelana ne-voltage (ukuphakama):isigaba-kuya-isigaba, isigaba ukuya emhlabeni,/kuzo zonke izindawo ezivulekile othintana nazo | kV | 185/215 | |
Imvamisa yamandla imelana ne-voltage yesifunda esisizayo kanye nesifunda sokulawula | V/1 iminithi | 2000 | |
Isilinganiso sokuvama | Hz | 50 | |
Ilinganiselwe ngokuphulwa kwesekethe emfushane | kA | 20, 25, 31.5 | |
Ilinganiselwe isekethe emfushane yokwenza yamanje | kA | 50, 63, 80 | |
Isilinganiso esiphakeme sokumelana nokumelana namanje | kA | 50, 63, 80 | |
Ilinganiselwe isikhathi esifushane ukumelana nobude besikhathi samanje/esilinganiselwe sesiyingi esifushane | kA/4s | 20, 25, 31.5 | |
Impilo yemishini | izikhathi | 1000 | |
Isikhathi sokuvala | ms | 50~100 | |
Isikhathi sokuvula | ms | 35-60 | |
Kukalwe ukulandelana kokusebenza | O-0.3s-CO-180s-CO |
Isakhiwo
Lo mkhiqizo uhlukaniswe izingxenye ezimbili: iKhabhinethi ne-VCB. Ikhabethe lenziwe ngepuleti lensimbi egobile futhi lihlanganiswe namabhawudi ngemuva kokufafaza. Ngokwezici zokusebenza, ingahlukaniswa ibe izingxenye ezine: igumbi elincane lebhasi, igumbi lensimbi edluliselwe, igumbi le-VCB, igumbi lekhebula kanye negumbi lebhasi, ingxenye ngayinye ihlukaniswe ngokuhlukaniswa kwensimbi okusekelwe phansi. Izinga lokuvikela le-switchgear ebiyelwe yi-IP4X; lapho kuvulwa umnyango wegumbi le-VCB, idigri yokuvikela i-IP2X.
I-switchgear inezikimu zesekethe eziyinhloko ezifana ne-cable inlet kanye ne-outlet, i-inlet ne-outlet engaphezulu, ukuxhumeka kwebhasi, ukunqanyulwa, i-voltage transformer, nesibambisi sombani. I-busbar ithatha ukufakwa okuhlanganisiwe, futhi isigaba esiphakathi nezixhumi zifakwe imikhono evikelayo eyenziwe ngezinto ezibamba ilangabi. Amakhabhinethi aseduze we-busbar eyinhloko ahlukaniswe imikhono yebhasi, engavimbela ngokuphumelelayo ingozi ekusakazeni futhi idlale indima yokwesekwa kwebhasi eyinhloko. Igumbi lekhebula lifakwe inkinobho yomhlaba, idivayisi yokuvikela i-overvoltage, njll.
Kukhona ishutha yensimbi yokuphepha phambi kwebhokisi lokuxhumana. I-shutter yezokuphepha engaphezulu nephansi ivuleka ngokuzenzakalelayo lapho i-VCB isuka endaweni yokunqamula/yokuhlola iye endaweni yokusebenza, futhi ivaleka ngokuzenzakalelayo lapho i-VCB ihamba ibheke kolunye uhlangothi, inqamuka ngempumelelo ku-voltage ephezulu. Ukuxhumana phakathi kweswishi eyinhloko, i-VCB, ukushintshwa komhlaba kanye nomnyango wekhabhinethi kusebenzisa indlela yokuxhuma eyimpoqo ukuze kuhlangatshezwane nezidingo zokusebenza "zokuvimbela ezinhlanu".
I-circuit breaker isebenzisa i-screw rod drive propulsion mechanism kanye ne-clutch overrunning. I-screw rod feed nut ingasetshenziswa kalula ukuhambisa i-VCB phakathi kwendawo yokuhlola nendawo yokusebenza. Ngosizo lwempahla yokuzikhiya ye-screw rod nut, i-VCB ingakhiywa ngokuthembekile endaweni yokusebenza ukuze ivimbele i-VCB engozini ebangelwa ukubaleka ngenxa yamandla kagesi. I-clutch eyeqisayo isebenza lapho i-VCB ibuyela endaweni yokuhlola nalapho ifika endaweni yokusebenza. Kwenza i-shaft yokusebenza kanye ne-screw shaft zikhiphe ngokuzenzakalelayo futhi zingasebenzi, okungase kuvimbele ukusetshenziswa kabi futhi kulimaze indlela yokuphakelayo. Amanye ama-VCB asebenzisa indlela ye-lever feed. Indawo yokusebenza yokuhlola ikhiywe ngezikhonkwane zokubeka.
Ubukhulu obuphelele bekhabhinethi yilezi: W×D ×H (mm): 1400×2800×2600
Imidwebo yeSikimu Sesifunda Esiyinhloko
Uhlelo oluyisisekelo NO. | 1 | 2 | 3 | 4 | 5 | |
Umdwebo wesikimu sesifunda esikhulu | ||||||
Izingxenye zesekethe eziyinhloko | Vacuum circuit breaker ZN85-40.5 | 1 | 1 | 1 | 1 | 1 |
I-transformer yamanje i-LZZBJ9-35 | 1-3 | 1-3 | 4-6 | |||
I-voltage transformer JDZ9-35 | ||||||
Ukubopha i-HY5WZ2 | 0 noma 3 ngokuzithandela | |||||
Ukushintsha komhlaba JN24-40.5 | 0-1 ngokuzikhethela | |||||
Isibonisi esishajiwe | 0-1 ngokuzikhethela | |||||
I-Fuse XRNP-35 | ||||||
Isiguquli samandla i-SC9-35 | ||||||
Isicelo | I-overhead inlet (i-outlet) |