I-FZRN61 switch break break with disconnect switch kanye ne-earth switch

Incazelo emfushane:

Indoor AC high voltage miniaturized vacuum load break switch
• 3 isigaba
• 3 indawo yokusebenza
• kuhlanganiswe
• ngeswishi yokunqamula kanye neswishi yomhlaba
• ukusebenza kwesokudla/kwesokunxele, ukufakwa okubheke phansi kuyatholakala

Imininingwane Yomkhiqizo

Omaka bomkhiqizo

Uhlolojikelele

• I-FZN61-12DG/630-20 kanye ne-FZN61-12DG/1250-25 yangaphakathi ye-AC high voltage miniaturized vacuum load break switch iyimishini yokushintsha amandla kagesi ezigaba ezintathu eziphezulu ezinama-voltage akalwe angu-12kV kanye nemvamisa elinganiselwe engu-50Hz, isetshenziselwa ukushintsha amaza okulayisha. , i-loop yamanje evaliwe, i-transformer engalayishi kanye yamanje yokushaja ikhebula, futhi yenza isifunda esifushane samanje. Iswishi yekhefu le-vacuum enezimo ezintathu ezincane efakwe iswishi yokunqamula phezulu kanye neswishi yomhlaba ezansi ingamelana namandla wesekethe emfishane.

• FZRN61-12DG/200-31.5 AC high voltage miniaturized vacuum load break switch-fuse inhlanganisela yeyunithi iyimishini yasendlini yokushintsha amandla kagesi aphezulu, ihlanganisa i-FZRN61-12DG i-miniaturized load break switch kanye ne-S □LAJ-12 (XRNT □-10) yamandla kagesi aphezulu i-fuse enomkhawulo wamanje. Ingakwazi ukwephula noma iyiphi i-current kuze kufike ku-short-circuit current; i-switch break break iphula i-current esebenzayo, i-fuse iphula i-current, futhi ijoyinti liphula noma imuphi umsinga phakathi kwamandla asebenzayo kanye ne-short-circuit current ephelele. Ngesikhathi esifanayo, i-fuse ivula inkinobho yekhefu lomthwalo ngokusebenzisa isiteleka sayo.

 

Uhlobo Incazelo

 

Sebenzisa Izimo

• Izinga lokushisa lomoya elizungezile: -30℃~+40℃;

• Ukuphakama: ≤1000m; ngaphezu kuka-3000m kungenziwa ngezifiso;

• Umswakama ohlobene: isilinganiso sansuku zonke ≤95%, isilinganiso sanyanga zonke ≤90%;

• Amandla okuzamazama komhlaba: ≤8 degree;

• Izindawo ezingenabungozi bomlilo nokuqhuma, ukugqwala kwamakhemikhali nokudlidliza okukhulu;

• Iziqu zokungcola: II.

 

Amapharamitha wezobuchwepheshe kanye nokusebenza

CHA.

Into

Iyunithi

Iswishi yekhefu lokulayisha i-vacuum

Iyunithi yenhlanganisela ye-vacuum break break-fuse FZRN61-12(D)/T200-31.5

FZN61-12(D)/T630-20

FZN61-12(D)/Т1250-25

1

I-voltage elinganiselwe

kV

12

2

Isilinganiso sokuvama

Hz

50

3

Ikalwe okwamanje

A

630

1250

200

4

Ilinganiselwe isikhathi esifushane ukumelana namanje

kA

20, 25

5

Isilinganiso esiphakeme sokumelana nokumelana namanje

kA

50, 63

6

Ilinganiselwe isekethe emfushane yokwenza yamanje

kA

50

63

80

7

Ilinganiswe ngokulayisha okusebenzayo okwamanje

A

1250

1250

8

Ilinganiselwe ngokunqamuka kweluphu evaliwe

A

1250

1250

9

I-transformer engalayishiwe ephukile

kVA

2000

10

Iphutha lamanje

A

20

11

Ulayini nentambo yokushaja okwamanje ngaphansi kwezimo zephutha lomhlaba

A

20

12

Ilinganiswe ngokuphuka kwesiyingi esifushane

kA

 

31.5/50 (kuya ngefuse)

13

Isilinganiso sokudlulisa samanje

A

3150

14

Isikhathi sokuvula esilungisiwe

ms

45

15

Imvamisa yamandla imelana ne-voltage (1min)

kV

Isigaba-kuya-isigaba, isigaba-kuya-emhlabeni, kuyo yonke indawo yokuxhumana evulekile: 42, ngaphesheya nqamula othintana nabo abavulekile: 48

16

Umbani umelane ne-voltage

kV

Isigaba-kuya-isigaba, isigaba-kuya-emhlabeni, kuyo yonke indawo yokuxhumana evulekile: 75, ngaphesheya nqamula othintana nabo abavulekile: 85

17

Impilo yemishini

izikhathi

> 10000

 

Umdwebo Wokuhlaziya Umhlangano Womkhiqizo

1. i-outlet ephezulu 2. nqamula switch 3. i-insulating base 4. uxhumano oluguquguqukayo 5. isibambi se-fuse esiphezulu

6. i-fuse 7. isibambi se-fuse esiphansi 8. ipuleti lohambo 9. indawo ephansi 10. uhlaka lwensimbi 11. isiphazamisi sevacuum

12. indlela yasentwasahlobo 13. iphaneli yokusebenza 14. ukushintsha komhlaba

Isingeniso Sesakhiwo Somkhiqizo

• I-vacuum yokunqamula iswishi yekhefu ingumkhiqizo ojwayelekile; isakhiwo sohlaka: isakhiwo esihlangene, iswishi yokunqamula edidiyelwe, iswishi yekhefu le-vacuum load, i-fuse, iswishi yomhlaba iyonke imikhiqizo kagesi enamandla kakhulu esebenza kakhulu.

• Usayizi omncane: ububanzi esimweni esivulekile nesivaliwe: ububanzi be-vacuum load break switch ≤299mm.

• Amapharamitha aphezulu: umthamo olinganiselwe we-vacuum load break switch ufike ku-1250A; umthamo wamanje olinganiselwe weyunithi yenhlanganisela ye-switch-fuse ifinyelela ku-200A, engavikela i-transformer engu-2000kVA.

• Iswishi yokunqamula ulayini ongenayo ixhunywe neswishi yomhlaba. Ngemva kokuvulwa kweswishi yomhlaba, inkinobho yokunqamula umugqa ongenayo izovalwa ngesenzo esifanayo.

• Iswishi yokunqamula ejikelezayo enokwephuka okubonakalayo ngemva kokuvula.

• Kukhona ukuxhuma komshini phakathi kweswishi yokunqamula ukulayisha kwe-vacuum kanye neswishi yokunqamula (umhlaba) ukuvimbela ukusebenzisa kabi. Qinisekisa ukuthi iswishi yekhefu le-vacuum ingavalwa ngemva kokuba iswishi yokunqamula ivaliwe; iswishi yokunqamula ingavulwa kuphela ngemva kokuvulwa kweswishi yekhefu lokulayisha kwe-vacuum.

• I-switch break break ingafakelwa umshini wokusebenza kagesi, ongugesi kanye nesandla, ingakwazi ukubona isilawuli kude.

• I-switch eyisiza yokuzikhethela, i-shunt kanye nokukhululwa kwe-overcurrent.

• Ijubane lokuvula nokuvala le-vacuum load break switch alithintwa ukusebenza okwenziwa ngesandla.

• Indlela yokulwa nokungasebenzi kahle ihlangabezana nezidingo “zezivimbelo ezinhlanu” zesethi ephelele yemishini yamandla kagesi aphezulu.


  • Okwedlule: