I-FN5-12 Series Indoor High Voltage Air Load Break Switch

Incazelo emfushane:


Imininingwane Yomkhiqizo

Omaka bomkhiqizo

I-FN5-12 uhlobo lwe-AC high voltage load brek switch yasendlini (ngemuva kwalokhu ebizwa ngokuthi i-load break break) ama-apula kunethiwekhi ye-AC 50Hz 12kV, yokuphula umthwalo wamanje kanye nokuvala isekethe yesifunda esifushane. Iswishi yekhefu lokulayisha ene-fuse inganqamula umjikelezo wesifunda esifushane ukuze kuvikelwe ukushintsha.

Iswishi yekhefu lokulayisha ingasetshenziswa ngohlobo lwe-CS6-1 lwendlela yokusebenza yezandla, futhi lo mkhiqizo okhethekile usebenzisa indlela yokusebenza ye-CS manual.

e1ee3042

Isicelo

I-FN5-12 yohlobo lwe-AC yasendlini ye-high voltage break switch (ngemuva kwalokhu ebizwa ngokuthi yi-load break switch) isebenza kunethiwekhi ye-AC 50Hz 12kV, yokuphula umthwalo wamanje nokuvala isekethe yesifunda esifushane. Iswishi yekhefu lokulayisha ene-fuse inganqamula umjikelezo wesifunda esifushane ukuze kuvikelwe ukushintsha.

Iswishi yekhefu lokulayisha ingasetshenziswa ngohlobo lwe-CS6-1 lwendlela yokusebenza yezandla, futhi lo mkhiqizo ukhethekile usebenzisa i-CSumlomoindlela yokusebenza ngesandla.

Uhlobo Nencazelo

dfb

Sebenzisa imvelo

a. Ukuphakama

b. Umoya we-ambientrmFre: -25~+40°C, (indlela yokusebenza yemoto〉-5°C);

c. Umswakama ohlobene: isilinganiso sansuku zonke esingu-

d. Umoya osendaweni ongenakho ukungcoliswa okusobala, njengegesi ebolayo noma evuthayo, umhwamuko wamanzi, njll.

e. Ngaphandle kokudlidliza okuqinile.

Idatha yobuchwepheshe

4.1 Ithebula 1 lamapharamitha wokushintsha kwekhefu lokulayisha umthwalo 1

Igama

Iyunithi

Inani

I-voltage elinganiselwe

kV

12

I-voltage ephezulu yokusebenza

kV

12

Isilinganiso sokuvama

Hz

5.

Ikalwe okwamanje

A

400 630
Ilinganiselwe isikhathi esifushane ukumelana namanje (i-thermal stability current)

kA/S

12.5/4 20/2
Isilinganiso esiphakeme sokumelana namanje (i-dynamic stability current)

kA

31.5 50
Ilinganiselwe ngokunqamuka kweluphu evaliwe

A

400 630
Isilinganiso samandla okulayisha ukunqamuka kwamanje

A.

400 630
Isilinganiso samandla esingu-5% sokulayishwa kwe-breaking current

A

20 31.5

Isilinganiso sokushaja kwekhebula okwamanje

A

10

Kulinganiselwe ukuphulwa kwe-transformer yokulayisha 1250kVA akukho mthwalo

i-transformer yamanje

Isilinganiso sokuvala sesifunda esifushane

kA

31.5 50
Layisha izikhathi zokuphuka zamanje

Layisha/izikhathi

100%/20 30%/75

60%/35 5%/80

1minthi imvamisa yamandla w;nstana voltage (RMS), isigaba-to-isigaba / isoktmg ukuphuka

kV

42/48

Imvamisa yamandla i-v^tnstand voltage phakathi kokuhlukaniswa kwamafracture

kV

53

Umfutho wombani umelana ne-voltage ukuya emhlabathini(ukuphakama), ukuhlukana kwesigaba kuya kwesinye/okuhlukanisayo

kV

75/85

Ukuvula/ukuvala itorque yokusebenza

I-Nm(N)

90(80) 100(200)

Qaphela: Ingxenye ye-FN5-12D esekelwe phansi yeswishi yokulayisha enomthamo wamanje wokwenza isiyingi esifushane.

4.2 Ithebula lepharamitha ye-Fuse yobuchwepheshe2

Imodeli

I-voltage elinganiselwe ye-KV

Fuse

Ikalwe okwamanje

A

Ilinganiselwe ngokuphulwa kwe-KA yamanje

Isilinganiso samanje se-fuse-elementi

I-RN3

12

50

12.5

2, 3, 5, 7.5, 12, 15,20,30, 40, 50

75

75

100

100

200

150 200

I-SDL*J

12

40

50

6.3, 10, 16, 20, 25, 31.5,40

SFL*J

12

100

50, 63, 71, 80, 100

SKL*J

12

126

125

Ubukhulu bokubukeka nokufakwa (mm)

Umfanekiso 1 FN5-12

svd

1. I-Framework 2. Isivikelo seposi 3. Ibhodi lezintambo ezinebhodi 4. I-Blade 5. Isicishamlilo se-arc

6. I-Torsional spring kanye ne-pin yayo 7. Ibha yomhlahlandlela 8. I-Wiring board 9. I-Lever

10. I-switch yokulayisha ehambayo 11. Indlela yokushaja yasentwasahlobo 12. Indlela yokusebenza

Umfanekiso 2 FN5-12D

svv

1. I-Framework 2. I-Earth blad, 3. 7, i-rth switch ihamba iphethe 4. Isivikeli seposi

5. Umhlaba onyakazayo 6. Ibhodi lezintambo ezikhazimulayo 7. I-Blade 8. isicishamlilo se-arc

9. Dweba intwasahlobo kanye+i-spring pin bearing 10. Ibha yomhlahlandlela 11. Ibhodi lezintambo 12. I-Lever

13.I-switch switch yokulayisha 14. Umshini wokushaja wokushintsha kwentwasahlobo wokulayisha

15. Umhlaba swl,h ^indlela yokushaja indandatho 16. Indlela yokusebenza yeswishi yokulayisha

17. Indlela yokusebenza ye-Er rth vi ch 18. Indlela yokuxhumanisa

Fig.3I-FN5-12R(S)

svv

1. I-FN5-12R load sv 2. Ibhodi lezintambo ze-Bering fuse 3. Isixhumanisi se-Fuse 4. Ibhodi lezintambo ze-Fuse

5. Isisekelo se-Fuse

Fig.4I-FN5-12DR

sdvre

Imodeli ye-MechanismI-CS6-1

csn

Imodeli ye-Fuse

H

h

I-SDL*J,SFL*J,I-SKL*J

935

530

735 I-RN3-10

990

585

5=75

1040

635

1. FN5-12D umthwalo s.'

5. Isisekelo se-Fuse

Fig.4I-FN5-12R(S)

kabi

1. FN5-12 umthwalo swi,c:i 2. Bering,ibhodi lokufaka izintambo 3. I-Fuse 4. Ibhodi lokuhlanganisa i-Fuse 5. Isisekelo se-Fuse

Umfanekiso 6 FN5-12DR(S)

dfb rt

1. Iswishi ye-FN5-12D 2. Ibhodi lokufaka izintambo ze-Bering 3. I-Fuse 4. Ibhodi lezintambo ze-Fuse

5. Fusezimbili6. I-Interlock mechanism

Umfanekiso 7 FN5-12R(D)L

qq

1. Ngaphansi kohlaka 2. Isivikelo 3. I-Fuse 4. Idivayisi ye-Tripper 5. Othintana naye onyakazayo 6. Isicishamlilo se-arc

7. Ibha yomhlahlandlela 8. Ukuthintana okuqinile 9. Indlela yokuvula/yokuvala 10. Idivayisi yokukhiya

11. Indlela yokusebenza yeswishi 12. Iswishi yomhlaba


  • Okwedlule:
  • Olandelayo: