I-FN12-12 ye-HV air load break switch iyisisetshenziswa se-AC 50Hz 12kV esinezigaba ezi-3.
♦ Indlela yokufaka: ifakwe ngaphambili, ifakwe ohlangothini, ifakwe phezulu;
♦ Indlela yokusebenza: indlela yokusebenza yasentwasahlobo, uhlobo lwezandla kanye nohlobo lukagesi olutholakalayo;
♦ Uhlobo lokusebenza: ukusebenza kwesokudla kanye nokusebenza kwesokunxele;
♦ Isicelo: i-switchgear engu-12kv yangaphakathi.
Izimo Zemvelo
♦ Izinga lokushisa lendawo: -25°C~+40°C;
♦ Ukuphakama:
♦ Umswakama ohlobene: isilinganiso sansuku zonke esingu-
♦ Amandla okuzamazama komhlaba:
♦ Ibanga lokungcola: II;
♦ Izindawo ezingenamlilo, ukuqhuma, ukugqwala kwamakhemikhali kanye nokudlidliza okukhulu.
Imingcele Eyinhloko Yezobuchwepheshe
CHA | Into | Iyunithi | FN12-12D/6 30-20 | I-FN12-12RD/1 25-31.5 | ||
1 | I-voltage elinganiselwe | kV | 12 | 12 | ||
2 | Isilinganiso sokuvama | Hz | 50 | 50 | ||
3 | Ikalwe okwamanje | A | 630 | 125 | ||
4 | 1min imvamisa yamandla imelana ne-voltage (Isigaba ukuya emhlabeni, phakathi kwezigxobo, othintana nabo abavulekile) | Isigaba-to-earth, isigaba-to-isigaba | kV | 42 | 42 | |
Ukuqhekeka okuhlukanisayo | 48 | 48 | ||||
5 | Isilinganiso sombani imelana ne-voltage (Isigaba ukuya emhlabeni, phakathi kwezigxobo, othintana nabo abavulekile) | Isigaba-to-earth, isigaba-to-isigaba | kV | 75 | 75 | |
Ukuqhekeka okuhlukanisayo | 85 | 85 | ||||
6 | Ilinganiselwe isikhathi esifushane ukumelana namanje (i-thermal stability current) | Layisha ikhefu switch | kA | 20 | ||
Ukushintsha komhlaba | 20 | |||||
7 | Ilinganiselwe ubude besifunda esifushane (isikhathi sokuzinza kwe-thermal) | Layisha ikhefu switch | s | 4 | ||
Ukushintsha komhlaba | 2 | |||||
8 | Ilinganiselwe isekethe emfishane eyenza yamanje (isiqongo) | kA | 50 | |||
9 | Ikalwe okwamanje | Ukulayisha okusebenzayo kwamanje | A | 630 | ||
I-loop breaking current | 630 | |||||
5% osebenzayo wokunqamuka kwamanje | 31.5 | |||||
Intambo yokushaja yamanje | 10 | |||||
Umthamo we-transformer ongalayishi | kVA | 1250 | ||||
10 | Isilinganiso sokuphulwa kwesekethe emfushane (khawulela i-fuse yamanje) | kA | 31.5 | |||
11 | Isilinganiso sokudlulisa samanje | A | 1200 | |||
12 | Impilo yemishini | izikhathi | 2000 | 2000 | ||
13 | Amandla okukhipha umshayi | J | 1±0.5 |
Umdwebo Wesakhiwo Esijwayelekile Nosayizi Wokufaka (iyunithi: mm)
♦ FN12-12D (ukusebenza kwesobunxele okubekwe eceleni)
♦ FN12-12D (ukusebenza kwesokunxele okuphetshiwe)
♦ FN12-12RD (umsebenzi obekwe kwesokunxele ngaphambili)
♦ I-FN12-12RD (ukusebenza kwesobunxele okufakwe ngaphambili)